Case Study: Inrush Current
In Transformers
Suppose we have a 2.0KVA transformer with the
following specifications:
Peak Inrush Current occurs in one cycle = 564 Amps as measured on the scope.
Practical Max Inrush Current occurs in 5 cycles = 188.0 Amps as measured on the
scope.
Input Voltage = 120VAC
Ambient temperature = 80?C.
Frequency = 60 Hz.
Efficiency of transformer = 70%.
Select a thermistor which would reduce the inrush current in the inductive
circuit described above
SOLUTION:
- Calculate the Steady State Current
(KVA of transformer)
/ (efficiency of transformer) X (Minimum Input voltage)
2.0 KVA / (0.70) X (90) = 31.75 Amps.
- Calculate the maximum amount of Energy that the Thermistor should handle.
Inductive
Energy = ? X (L) (I)**2 I Peak
564 Ohms Inductive Reactance = XL = 2 X (p) X (F) X (L)
Line voltage / Max peak Current for One cycle.
120 VAC / 564 Amp = 0.213 ohm.
- Calculate the Inductance.
L = (XL) / (2) X (p) X (f)
= (0.213W) / (2) X (3.142) X (60)
= 0.000565 = 565 Milli Henry.
- Hence the Energy
= ? X (L) X ( I)**2
= ? X ( 0.000565) X (564)**2 @ 90.0 Joules.
- Since the Ambient is at 80?C and thermistors are rated up to 65?C for their
operating current, then a derating factor must be taken in to account.
Using
the de-rating curve at 80?C use 90% of max rated Steady State Current.
= 0.90 X 36 Amps = 32.40 Amps.
- You can use any of the devices rated up to 36.0 Amp to meet your SSI and
Energy Requirements.
- See the charts for part numbers. (i.e. SL32 0R536 OR SL32 1R036).
|